Smoke hatch DYMOZOR-100

Price
On request
Brand
WINDCOM
Country
Uzbekistan
Supplier
WINDCOM
City
Tashkent

Smoke exhaust hatch DYMOZOR®-100 is designed for installation on a flat roof of a building or on a roof with a slope of up to 14 degrees, and for use in smoke-exhaust ventilation systems with natural draft.

Recommended for installation on single-storey buildings of large area. In addition to its main purpose of removing combustion products, it can be used for ventilating the premises. The version with a transparent cover also provides additional natural lighting of the premises.

Design:

- Standard (C);

- Modular (M);

- Modular-left (ML);

- Modular-right (MP).

Housing:

- Straight, 500 mm high, with a 10-degree slope angle, made of galvanized steel;

- A support flange for fixing to the roof structure is provided at the bottom;

- Thermal insulation of foil-faced mineral wool, 50 mm thick;

- A heating cable is installed to protect the cover from freezing to the frame;

- For M/ML/MP designs, structural elements for connecting hatches/skylights are provided.

Cover:

- Single-leaf swing cover, available in three types;

- Consists of a steel load-bearing frame made of cold-rolled sheet and infill. It is attached to the housing by multi-axis hinges, with an opening angle of at least 90 degrees. The hinges are located inside the unit, which completely prevents them from icing up and makes waterproofing roofing material easier and higher-quality to install;

- Equipped with an end-position sensor;

- The cover type should be selected taking into account the required heat transfer resistance set by SP 50.13330.2012 for the specific climatic region;

Actuator:

- One rod electric actuator, branded by the company «VEZA», 24 V supply, 1600/3000 N force, installed inside the hatch under the cover. For dimension «B» less than 1000 mm the push force is transmitted directly to the cover, for larger sizes through a lever mechanism;

- The actuator force is selected based on the snow load of the intended operating region in accordance with SP 20.13330.2016 «SNiP 2.01.07-85* Loads and actions».

Painting:

- Powder coating in signal grey RAL 7012 ;

- Other colours from the RAL catalogue are available on special order.

Specifications

  • Purpose: smoke extraction in case of fire
  • Type: roof-mounted
  • Number of sashes (flaps): single-sash
  • Sash (flap) type: insulated opaque / polycarbonate transparent / architectural transparent with single-, double- or triple-layer dome
  • Number of electric actuators: 1 pcs
  • Electric actuator type: rod-type reversible
  • Actuator supply voltage: 24 V
  • Maximum snow load zone: V
  • Maximum wind load: 12 m/s
  • Base height (housing depth): 500 mm
  • Minimum opening angle: 90 deg.
  • Maximum opening time: 90 s
  • Permissible installation angle (roof slope): 0 ... 14 deg.
  • Seismic resistance on the MSK-64 scale: 9 points
  • Sash heating available
  • Internal arrangement of rotary hinges
  • Rectangular working cross-section.