Tip NIM-35.

Price
111 675,2 UZS
Country
Uzbekistan
Supplier
ALFA POWER SOLUTIONS
City
Tashkent

Designed for hermetic crimping of terminations on multi-core cables by compression. The insulating material is a polymer resistant to ultraviolet radiation and weather conditions. The design of the product ensures tightness at 6 kV, 50 Hz for 1 minute at a depth of 1 meter. To achieve these parameters, the corresponding layer of insulation must be stripped from the cable. The stripping length is indicated on the tip. The stripping boundary must be even, and the cable insulation thickness must remain at the same level up to the stripping boundary. The cable must be inserted into the product all the way to the stop. Crimping must be performed from the center toward the edge, observing the crimping boundary and the number of crimps indicated on the product. For load-bearing cables, the permissible mechanical loads on the crimped connection are: