Coupling Coupling Stp 3 70/95/120

Price
960 596 UZS
Brand
ПЗЭМИ
Country
Uzbekistan
Supplier
ALFA POWER SOLUTIONS
City
Tashkent

The connecting sleeve is designed for joining three-core power cables rated 6 and 10 kV with paper oil-impregnated insulation, with or without armor, in a lead or aluminum sheath.

- Heat-shrink connecting cable sleeves are designed for joining power cables with or without armor, and cables with paper oil-impregnated insulation with a common lead or aluminum sheath, rated up to 6 and 10 kV.

- The connecting sleeves comply with the requirements of TU 3599-006-97284872-2006 and GOST 13781.0-86 (certificate of conformity No. 0061261);

- Connecting sleeves are produced for 3 cable cross-section ranges: from 25 to 50 mm2, from 70 to 120 mm2, from 150 to 240 mm2.

Sleeves can be installed on the following cable types: ASB, AABl, ASShv, AAShv, SB and others;

- Heat-shrink sleeves use a special sealant that equalizes the electric field stress. The sealant creates reliable insulation of the cable stripping root against moisture penetration, is oil-resistant, and significantly reduces the risk of insulation breakdown.

Thick-walled insulating heat-shrink cuffs at the core junctions are made of a material that equalizes electric field stress, which significantly reduces the risk of insulation breakdown. The hot-melt adhesive applied to the inner surfaces of the heat-shrink elements provides a reliable barrier against moisture penetration.

- Heat-shrink connecting sleeves also use a special sealant that equalizes the electric field stress. The sealant creates reliable insulation of the cable stripping root against moisture penetration, is oil-resistant, and significantly reduces the risk of insulation breakdown.

- An interphase spacer is installed between the cable cores, creating additional insulation and correctly geometric core separation, and also providing additional structural rigidity.

- A special mastic applied into the interphase space eliminates voids and prevents air ionization in them, which positively extends the service life of the connecting sleeve.

- For attaching the grounding wire to the metal sheath of the cable, a constant-pressure spring is provided for fast and reliable connection. Using the constant-pressure spring prevents damage to the paper insulation under the aluminum sheath of the cable, provided soldering is carried out with high-melting solder "A".

- Cable connecting sleeves are available in two versions. A kit for installation with crimp cable lugs (sold separately). This installation requires additional equipment such as mechanical or hydraulic presses for crimping cable lugs.

A kit for installation with shear-bolt lugs (included with the connecting sleeve). For convenient installation of bolted lugs, the NMB-4 tool can be used.

Size marking decoding:

C - type: connecting sleeve

T - heat-shrink

p - presence of an insulating glove

10 - operating voltage 10 kV

70/120 - cable cross-section 70…120 mm2