Mounting glass STAM-415

Price
On request
Brand
WINDCOM
Country
Uzbekistan
Supplier
WINDCOM
City
Tashkent

STAM 415 installation sleeves are intended for installation next to OSA fans in exhaust and supply smoke ventilation systems, in order to prevent warm air from leaking out of the premises through the shaft and duct systems, in accordance with clauses 7.11 g) and 7.17 c) of the code of practice SP 7.13130.2013. STAM 415 is mounted on an inclined surface.

Design:

General industrial (H);

Corrosion-resistant (K1).

The insulated, thermally insulated STAM 415 is a box-type structure consisting of a welded steel frame that carries the main load, inside which a square-section duct and a PROK… valve (with a fire resistance rating of EI120), made of galvanized or stainless steel, are fixed. The side faces of the frame are fully covered with galvanized steel panels. Non-combustible heat-resistant thermal insulation is located between the frame and the duct. On the outside, the frame has a support surface for installation and fastening to the load-bearing part of the roof.

The connection to the ventilation duct is made with bolts through the mounting flange.

STAM® 415 – with a built-in supply valve PROK-3.

Specifications

  • Design: General industrial (H), Corrosion-resistant (K1)
  • Intended for installation on KROS/UKROS/KROV/UKROV/OSA fans
  • Mounted on an inclined surface.