Roof smoke exhaust fan KROV-DUV

Price
On request
Brand
WINDCOM
Country
Uzbekistan
Supplier
WINDCOM
City
Tashkent

Purpose and operating modes:

Ventilation and air heating systems;

Sanitary and industrial installations;

Smoke exhaust ventilation systems.

KROV®-DU/DUV fans have a tall housing with free upward air discharge and low weight; the design protects the premises from atmospheric precipitation.

2013 modification: new reduced base plate and a new impeller with increased efficiency (up to 75%).

The fans deliver high airflow, high static pressure and low noise.

The fans can operate in smoke exhaust mode (DU) as well as in combined smoke exhaust and ventilation mode (DUV). More modifications are available for the DUV mode. The KROV®-DU model is limited to 120 minutes of operation. The impeller is mounted directly on the motor shaft.

The fans are equipped with high-quality 3-phase asynchronous single-speed motors. A frequency converter (VFD) with programmed different speeds can be used for the DUV mode.

Mounting dimensions on the base plate are unified with the KROS® roof fan.

Fans on the roof are easily installed using the 2012 modification of the STAM® mounting curb (with reduced mounting dimensions).

The fans can be operated in moderate (U), moderately cold (UHL) and tropical (T) climates, placement category 1 according to GOST 15150-69.

Operating conditions:

ambient temperature:

-from minus 45 to +40°C for moderate climate;

-from minus 60 to +40°C for moderate and cold climate;

-from minus 10 to +50°C for tropical climate;

average vibration velocity of external vibration sources at the fan installation sites not more than 2 mm/s.

Specifications

  • Execution:
  • - General industrial (H)
  • - Corrosion-resistant (K1,)
  • - Explosion-proof (V, VS)
  • - Explosion-proof corrosion-resistant (VK1, VSK1)
  • Air outlet: upward
  • Static pressure up to 2800 Pa
  • Flow rate: 1000 … 110000 m3/h
  • Climatic version: U, UHL, T, placement category 1.