Fire damper NERPA-KP

Price
On request
Brand
WINDCOM
Country
Uzbekistan
Supplier
WINDCOM
City
Tashkent

NERPA-KP marine-version high-pressure fire dampers are designed for local and remote closing of ventilation and air-conditioning ducts passing through fire-resistant bulkheads, in order to prevent combustion products from entering the premises during a fire and to ensure gas tightness of the premises when hazardous zones are extended.

These dampers are installed in insert parts in openings of hull structures of ventilation and air-conditioning systems with an operating pressure of up to 5000 Pa, and can be used in medium- and high-pressure ventilation and air-conditioning systems on mixed and inland-navigation marine vessels of all classes, types and purposes, on gas production platforms, floating drilling rigs, fixed offshore platforms, and civil and industrial construction facilities.

NERPA-KP dampers are manufactured as marine-version fire dampers of class A 60 or H 120. The body of NERPA-KP dampers consists of two parts connected by a heat-resistant spacer. NERPA-KP dampers are manufactured only in rectangular cross-section, duct version, with two connecting flanges.

Pivoting blades are mounted on axles inside the body. The contact zones between the blades and the body are protected by a seal and expanding material, and the blades close against each other with a locking-type seal. When opened, the blades do not extend beyond the outer dimensions of the body. The inner part of the blade is protected by heat-resistant material and additionally reinforced to prevent twisting under high-temperature exposure and to protect against deflection at pressures up to 5000 Pa.

The blades open in parallel motion. For versions "H", "V", "MS" and "VMS" the damper is made of carbon steel, and for versions "K", "VK", "VMSK" and "VMS" the damper is made of stainless steel. On special order, dampers can be manufactured with a paint coating.

The actuator on these dampers is an electric drive with spring return or a reversible type. For general-purpose dampers the electric drive is protected by a metal housing; in the explosion-proof version the electric drive is enclosed in a sealed capsule.

NERPA-KP fire dampers can operate in moderately cold or marine climates, placement categories 2 and 3 according to GOST 15150, and remain operational in the temperature range from -60 to +50 °C. They are resistant to vibration loads, shock-proof, and remain operational during prolonged heeling, trim and rolling. These dampers ensure reliable and stable operation in seismically active areas with a maximum design earthquake of 8 points. The full assigned service life of NERPA-KP dampers is 35 years.

When specified in the order, NERPA-KP dampers can additionally be equipped with return flanges for welding to the duct, with bolted connection to the damper through special gasket material that maintains the tightness of the joint and is approved for marine conditions. The dampers meet all RMRS and RKO requirements.

Specifications

  • Fire damper NERPA-KP class: A 60 or N 120
  • Operating pressure: up to 5000 Pa
  • Actuator: electric drive with spring return or reversible
  • Response delay:
  • - for electric drive with spring return: no more than 20 s,
  • - for reversible electric drive: no more than 30 s.
  • Return time to initial (safe) position:
  • - for electric drive with spring return - no more than 120 s
  • - for reversible electric drive - no more than 30 s
  • Rated supply voltage:
  • - drive = 24 or ~24 or ~220 (50 Hz)
  • - for power supply of position control circuits = 24 or ~24 or ~220 (50 Hz)
  • Climatic version: U2, U3, UHL2, UHL3, OM1, OM2, OM3