Liquid fan heat exchanger type KOMPAS-VT

Price
On request
Brand
WINDCOM
Country
Uzbekistan
Supplier
WINDCOM
City
Tashkent

KOMPAS-VT type liquid ventilator heat exchangers (fan coils) are designed to create and maintain the specified temperature parameters in the served premises of sea vessels of mixed and inland navigation of all classes, types and purposes, by heating, cooling and supplying recirculated air. KOMPAS-VT fan coils can also be used on gas production platforms, floating drilling units, stationary offshore platforms and civil and industrial construction facilities.

A distinctive feature of this type of fan coil is its compactness, seismic resistance, resistance to vibration, trim, heel and natural aggressive environments (sea air, high daily temperature fluctuations), relatively simple installation and a competitive price.

The fan coils have a modular design, which includes a fan, a heat exchanger, a condensate collection tray and, as options, water control valves and a drain pump. The design of the fan coils ensures interchangeability of all functional elements and of the modules themselves. The main element of the fan coil design is the housing heat exchanger. The heat exchanger has a welded or brazed structure and meets the most stringent tightness requirements. Heat exchanger tubes can be made of copper, copper-nickel alloy or stainless steel.

The fan coils use single-inlet fans. The fans used are designed for long continuous operation, have low energy consumption and a fairly low noise level. The characteristics of the fans used allow the fan coils to operate in duct ventilation systems; the standard free pressure at the fan outlet is 200 Pa. Water, water-glycol solutions and other heat carriers can be used as the heat-transfer fluid supplied to the liquid heaters.

KOMPAS-VT fan coils remain operational under the following conditions:

ambient air operating temperature from 0 °C to 40 °C;

long-term storage temperature from -40 to 50 °C and relative humidity of 98% (+35 °C).

rolling with an amplitude of 45 degrees and a period of 7–9 s;

long-term (unlimited time) inclination up to 15 degrees;

short-term (no more than three minutes) inclination up to 45 degrees.

vibration at frequencies from 2 to 80 Hz

a) vibration with a displacement amplitude of ±1 mm at frequencies from 2 to 13.2 Hz;

b) vibration with an acceleration of ±0.7 g at frequencies from 13.2 Hz to 80 Hz;

c) shocks with an acceleration of ±5.0 g at a frequency of 40 – 80 shocks per minute.

seismic activity – maximum design earthquake level of 8 points (acceleration 2 m/s²), while seismic forces may act in any direction in space.

KOMPAS-VT fan coils can operate in marine climate conditions, placement categories 3 and 4 per GOST 15150. The full assigned service life of the fan coils – at least 10 years, the established failure-free operating time – 7.5 thousand hours. KOMPAS-VT fan coils are manufactured taking into account RMRS requirements.

Specifications

  • Fan coil execution: general industrial / corrosion-resistant
  • Working pressure of heat carrier, MPa: not more than 1.6
  • Heat carrier temperature, degrees C: not more than 190
  • Working air temperature, degrees C: from 5 to 40 degrees C as standard, max. 65 degrees C, to be clarified when ordering
  • Permissible seismic activity: not more than 8 points
  • Number of size types: 7
  • Total excess pressure, Pa: standard 200
  • Nominal air flow rate, m3/h: from 400 to 1800
  • Heating capacity, kW: from 6 to 30
  • Cooling capacity, kW: from 2 to 10
  • Average noise level at nominal air flow rate, dB, not more than: 70
  • Filter cleaning class: standard G3
  • Type of heat / cold carrier (other types by agreement):
  • - water
  • - glycol solutions
  • Climatic design type: OM 3,4.