Roof fan UKROV

Price
On request
Brand
WINDCOM
Country
Uzbekistan
Supplier
WINDCOM
City
Tashkent

Purpose:

Ventilation systems – operating mode: T80;

Plumbing and industrial installations – operating mode: •T80 •T200.

UKROV® fans are specially designed for operation at low temperatures (down to minus 60 °C) in areas with heavy snowfall.

Design:

Corrosion-resistant (K1);

Explosion-proof, corrosion-resistant (VK1);

Explosion-proof, corrosion-resistant (VSK1) – for gas group IIC, hydrogen only, per GOST R 55026-2012.

UKROV® fans have a housing that is taller, with upward airflow discharge, and a reduced base plate. The roof with a rotating louver protects the internal volume and the electric motor from precipitation. All main fan components are made of stainless steel.

Impellers with increased efficiency are mounted directly on the motor shaft.

Mounting dimensions on the base plate are unified with KROS® roof fans.

Fans on the roof are easily installed using the STAM® mounting sleeve, 2012 modification (with reduced mounting dimensions).

UKROV fans are a higher-grade model than UKROS and can be installed in areas with extremely high snowfall.

Additional fan options are available; see the catalog section «Additional equipment».

Operation

Fans can be operated in moderate (U), moderately cold (UHL) and tropical (T) climates, placement category 1, per GOST 15150.

Operating conditions:

ambient temperature:

-from minus 45 to +40 °C for moderate climate,

-from minus 60 to +40 °C for moderate and cold climate,

-from minus 10 to +50 °C for tropical climate;

average vibration velocity of external vibration sources at the fan installation points not exceeding 2 mm/s;

Specifications

  • Execution: Corrosion-resistant (K1,), Explosion-proof corrosion-resistant (VK1, VSK1)
  • Air outlet: upward
  • Static pressure up to 2100 Pa
  • Flow: 1000 … 97000 m3/h
  • Climatic version: U, UKhL, T, placement category 1
  • For use at facilities with extreme requirements for service life and snowfall quantity.