Automatic switch EKF va-99ml 250/160a 3p 20ka

Price
On request
Brand
EKF
Country
Uzbekistan
Supplier
ALFA POWER SOLUTIONS
City
Tashkent

Circuit breaker VA-99 is a monoblock design consisting of a base and a cover with a front panel that has a window for the control handle and a plunger for the «Test» button, used to check the breaker's trip mechanism. The base is made of heat-resistant plastic that does not support combustion and serves as the supporting structure for the connection clamps, fixed and moving contacts with the arc-quenching system, the control mechanism, and the overcurrent protection unit. The cover encloses all moving elements of the control mechanism and the internal current-carrying parts.

For the full range of additional devices, see pages 155–161.

ATTENTION! The breaker lever has three positions: «ON», «OFF» and «TRIPPED». To switch on after a trip, move the lever from the intermediate position to «OFF», and then to «ON».

The breaker's control mechanism is built on the toggle lever principle and is equipped with a powerful return spring.

When the control handle is cocked, the insulating bar is set in motion, on which the spring-loaded movable power contacts with flexible connections are mounted. The bar rotates in side guides, providing not only the closing of the movable and fixed power contacts, but also the necessary travel to increase and equalize the pressure on the movable contacts. The action of the return spring is blocked by the elements of the toggle lever, which at that moment lie on one straight line, resting with one knee on the projection of the «Reset» rotary element and the control mechanism. The control mechanism is «reset» by means of a flat bar, acted upon through adjusting screws by the pushers of the bimetallic plates of the thermal releases and the electromagnets of short-circuit protection. The arc-quenching

system of the breakers is highly effective; however, when installing breakers in a closed volume of switchgear, it is necessary to take into account the possibility of arc combustion products being ejected upward up to 30 mm in the event of overcurrent protection tripping.

Wires or busbars from the power source are connected to the upper terminals of the breakers using bolts or clamps included in the delivery set. Wires or busbars to the load are connected to the lower terminals. Connection of wires and busbars from the power source from below, and of wires and busbars to the load from above, is permitted. In this case, all technical characteristics of VA-99ML remain unchanged.