Automatic switch EKF va-99ml 100/63a 3p 18ka

Price
On request
Brand
EKF
Country
Uzbekistan
Supplier
ALFA POWER SOLUTIONS
City
Tashkent

The VA-99 circuit breaker is a monoblock design consisting of a base and a cover with a front panel, which has a window for the control handle and a pusher for the 'Test' button – for checking the breaker's trip mechanism. The base is made of heat-resistant plastic that does not support combustion and serves as the supporting structure for the connection clamps, fixed and moving contacts with the arc-extinguishing system, the control mechanism and the overcurrent protection unit. The cover closes all moving elements of the control mechanism and the internal current-carrying parts.

For the full range of additional devices, see pages 155-161.

ATTENTION! The breaker lever has three positions: 'ON', 'OFF' and 'TRIPPED'. To switch on after a trip, move the lever from the intermediate position to 'OFF', and then to 'ON'.

The breaker control mechanism is built on the principle of a toggle lever and is equipped with a powerful return spring.

When the control handle is cocked, an insulating bar is set in motion, on which spring-loaded moving power contacts with flexible connections are mounted. The bar pivots in side guides, providing not only closing of the moving and fixed power contacts, but also the necessary travel to increase and equalize the pressure on the moving contacts. The action of the return spring is blocked by the elements of the toggle lever, which at that moment are on one straight line, resting with one knee on the projection of the 'Reset' rotary element and the control mechanism. The control mechanism is 'reset' by means of a flat bar, acted upon through adjusting screws by the pushers of the bimetallic plates of thermal releases and the electromagnets of short-circuit protection. The arc-extinguishing system of the breakers is very effective; however, when installing breakers in an enclosed volume of switchgear, it is necessary to take into account the possibility of upward ejection, up to 30 mm, of arc combustion products in case of overcurrent protection tripping.

Wires or busbars on the power source side are connected to the upper terminals of the breakers using the bolts or clamps included in the delivery set. Wires or busbars to the load are connected to the lower terminals. It is permitted to connect wires and busbars from the power source from below, and wires and busbars to the load from above. In this case all technical characteristics of VA-99ML remain unchanged.