High-density valves KEDR and KEDR-S


- Price
- On request
- Brand
- WINDCOM
- Country
- Uzbekistan
- Supplier
- WINDCOM
- City
- Tashkent
KEDR® and KEDR®-S are high-tightness dampers designed to regulate supply, recirculation or exhaust air in high-pressure ventilation systems, and also to seal the internal volume of ventilation ducts, with an operating pressure of up to 2500 Pa. Among other applications, this type of damper can also be used as a shut-off damper in medium-pressure systems where several fans do not operate synchronously.
In this case, the dampers are installed directly on the discharge and/or suction side of the fan and are used to prevent back-rotation of the impeller of a non-operating fan, which is unacceptable if it may start automatically.
The KEDR®-S damper is a frost-resistant version of the KEDR® damper, which guarantees reliable operation of the damper under a severe combination of humidity and low temperatures down to minus 60 °C.
Versions:
- General industrial (H);
- Corrosion-resistant (K);
- Explosion-proof (V);
- Corrosion-resistant and explosion-proof (KV).
The KEDR® and KEDR®-S damper consists of a box-type steel body reinforced with additional stiffening elements. The blades are made of a special volumetric steel profile and do not extend beyond the body outline. Damper kinematics: levers and rods on a rigid linkage. Bearing assemblies prevent the blade axes from skewing under pressure, which allows unobstructed flow regulation at maximum pressure.
The KEDR®-S damper is additionally equipped with a flexible self-regulating heating cable located at the junction of the blades and the actuator. In any configuration, the dampers remain operational regardless of spatial orientation.
As standard, the dampers can be equipped with VEZA electric actuators. On special order, dampers with BELIMO electric actuators or electric and pneumatic actuators from other manufacturers can be produced.
Specifications
- Purpose: shut-off, control
- Duct valve
- Operating pressure up to 2500 Pa
- Medium velocity up to 20 m/s
- Actuator: electric drive, handle
- Leakage class 2 (class 3 on special order)
- Blade opening: symmetrical
- Arbitrary spatial orientation
- Heat transfer resistance coefficient across valve section:
- - versions H, K, V, KV: 0.0008 m2*K/W
- - versions Ts, VTs: 0.0063 m2*K/W.
- Climatic version per GOST 15150-69: UKhL2, U3
- KEDR-S perimeter heater power:
- - rated power consumption of heated heater: 0.03 kW/m
- - rated power consumption of heated heater: 0.03 kW/m.
Similar products
Regulating valve RAGLAN
Mounting frame MRP
Mounting frame MRP
Mounting frame MRZ
Noise suppression plates PLAST
PLAG noise reduction plates
Universal fire damper KPU-2N
Universal fire damper KPU-1N
Universal fire damper KPU-1N
Fire-prevention check valve PROK
Fire-prevention check valve PROK
Fire damper GERMIK-DU
Company products
Check valve UKOL
Check valve UKOL
Check valve TULIP
Check valve NERPA-KO
Check valve KOL
Linear expansion compensator COM 560
Insulated vestibule valve GERMIKx2S
Insulated vestibule valve GERMIKH2P
Excess pressure relief valve KID
Universal fire damper KPU-DD
Universal fire damper KPU-DD
Universal fire damper KPU-2N