Universal fire damper KPU-DD

Price
On request
Brand
WINDCOM
Country
Uzbekistan
Supplier
WINDCOM
City
Tashkent

KPU-DD universal fire dampers are designed for automatic closing of ventilation ducts or openings in building enclosing structures. They are installed in general ventilation, air conditioning, exhaust and supply smoke control ventilation systems, as well as in systems for removing gas and smoke after a fire from premises protected by gas, aerosol or powder fire suppression systems.

IMPORTANT! Rectangular duct-type KPU-DD dampers retain their operability regardless of spatial orientation, provided the axis of rotation of their blades is horizontal. Wall-type KPU® dampers retain their operability only when installed vertically and provided the axis of rotation of the blades is vertical.

The "for NPP" version dampers (KPU®-A series) are designed for operation at nuclear power plants in accordance with the requirements of the "General Provisions for Ensuring the Safety of Nuclear Power Plants" (NP-001-15) and are a separate special version of the KPU® series dampers.

Information on these dampers is available upon request.

Purpose

-Double action (DD)

KPU®-DD double-action fire dampers (closed during a fire and opened after it) are designed for installation in general ventilation systems used to remove gases and smoke after a fire from premises protected by gas, aerosol or powder fire suppression systems, in accordance with SP 7.13130.2013 clause 7.13 b, c.

Version

-General industrial (N)

-Corrosion-resistant (K)

-Frost-resistant (MS)

-Frost-resistant corrosion-resistant (MSK)

-Explosion-proof (V) – except wall type

-Explosion-proof corrosion-resistant (VK) – for duct type

-Explosion-proof frost-resistant (VMS) – for duct type

-Explosion-proof frost-resistant corrosion-resistant (VMSK) – for duct type

Version by working medium flow parameters

Standard (0) – installation in systems with static pressure of no more than 2000 Pa for duct-type dampers and 700 Pa for wall-type dampers. Working medium velocity across the damper section no more than 15 m/s for duct-type dampers and no more than 13 m/s for wall-type dampers.

Damper type

- Wall type (1*ph)

- Duct type (2*ph)

Construction

The dampers consist of a rectangular-section housing made of galvanized steel (versions •N •MS •V •VMS) or stainless steel (versions •K •MSK •VK •VMSK), with a rotary-type blade installed inside. The blade is made entirely of fire-resistant material without metal cladding, which has low thermal conductivity, moisture resistance, frost resistance and environmental safety.

A version without blade protrusion is available (for duct type).

Actuator

- Electric actuator with spring return (P)

- Reversible electric actuator (R)

In the duct version the actuator is located only outside the damper; in the wall version it is located inside the damper.

Specifications

  • Fire resistance limit: EI 15
  • Heat transfer resistance coefficient across valve section: 0.69 m2·K/W
  • Response time:
  • - spring-return electric actuator: <= 20 sec
  • - reversing electric actuator: <= 30 sec.
  • Housing protection rating:
  • - electric actuator: IP54
  • - explosion-proof electric actuator: IP66.
  • Rated supply voltage, V:
  • - electric actuator: =24 or ~24 or ~220 (50Hz)
  • - position monitoring circuit: =24 or ~24 or ~220 (50Hz).
  • Actuator heater power:
  • - rated power consumption of heated heater: 0.02
  • - maximum starting power of heater at minus 10 degrees: 0.12.
  • Heater rated voltage: 220V (50Hz).