Universal fire dampers KPU-2N are designed to automatically close ventilation ducts or openings in the enclosing structures of buildings and are installed in general exhaust and supply ventilation systems, air conditioning, and exhaust and supply smoke ventilation systems, as well as in systems for removing gas and smoke after a fire from premises protected by gas, aerosol or powder fire suppression installations.
IMPORTANT! KPU-2N duct-type dampers of rectangular section retain their operability regardless of spatial orientation, provided that the axis of rotation of their blades is horizontal. KPU® wall-type dampers retain their operability only when installed vertically and with the axis of rotation of the blades vertical.
Purpose:
- Normally open (O);
- Normally closed (Z);
- Smoke (D).
Version:
- General industrial (N);
- Corrosion-resistant (K);
- Frost-resistant (MS);
- Frost-resistant and corrosion-resistant (MSK);
- Explosion-proof (V) – for duct type;
- Explosion-proof corrosion-resistant (VK) – for duct type;
- Explosion-proof frost-resistant (VMS) – for duct type;
- Explosion-proof frost-resistant corrosion-resistant (VMSK) – for duct type
Version by working medium flow parameters:
Standard (0) – installation in systems with static pressure of no more than 2000 Pa for duct-type dampers and 700 Pa for wall-type dampers. Working medium velocity in the damper cross-section no more than 15 m/s for duct-type dampers and no more than 13 m/s for wall-type dampers.
Damper type:
Wall type (1*f)
Duct type (2*f)
The damper is a rectangular-section casing made of galvanized steel (versions •N •V •MS •VMS) or stainless steel (versions •K •VK •MSK •VMSK). The parts of the casing are separated from each other by a thermal insulating spacer. Inside the casing there is a rotary-type blade made of fire-resistant material without metal cladding, which has a low thermal conductivity coefficient, moisture resistance, frost resistance and environmental safety. A version without blade projection (for duct type) is provided.
Actuator:
-Electric drive with spring return (for purpose •O);
-Electric drive with spring return and thermal fuse device TRU (for purpose •O);
-Reversible-type electric drive (for purpose •Z •D);
-Electromagnetic drive (for purpose •O •Z •D).
In duct-type dampers the actuator is located only outside the damper; in wall-type dampers it is located inside the damper.
Specifications
- Fire resistance limit: EI 120
- Thermal resistance coefficient across the damper cross-section: 0.69 m2×K/W
- Response time:
- - electromagnetic actuator: <=5 s
- - electric actuator with spring return: <= 20 s
- - electric actuator with reversible drive: <=30 s.
- Housing protection rating:
- - electromagnetic actuator: IP42
- - electric actuator: IP54
- - explosion-proof electric actuator: IP66.
- Rated supply voltage, V:
- - electric actuator: =24 or ~24 or ~220 (50 Hz)
- - electromagnetic actuator: =24 or ~220 (50 Hz)
- - position monitoring circuit: =24 or ~24 or ~220 (50 Hz).
- Power of the heating element (TEN) of the electric actuator:
- - rated power consumption of the heated TEN: 0.02
- - maximum starting power of the TEN at minus 10 degrees: 0.12.
- Rated TEN voltage: 220 V (50 Hz).
Similar products
Company products
High-density valves KEDR and KEDR-S
Insulated vestibule valve GERMIKx2S
Insulated vestibule valve GERMIKH2P
Excess pressure relief valve KID
Universal fire damper KPU-DD
Universal fire damper KPU-DD
Universal fire damper KPU-2N
Universal fire damper KPU-1N
Universal fire damper KPU-1N
Fire-prevention check valve PROK
Fire-prevention check valve PROK
Fire damper GERMIK-DU
Check valve UKOL
Check valve UKOL
Check valve TULIP
Check valve NERPA-KO
Check valve KOL
Linear expansion compensator COM 560
Excess pressure valve fire protection OXID
Smoke valve KED
Balancing valve CLUB
Hermetic ventilation valve GEK
Air check valve NERPA-KO
High Density Air Valve NERPA